Fire Protection Systems - Examples & Applications - Sprinkler Coverage
Fire detection, alarm, and suppression systems for building safety.
Open the complete lessonSprinkler Head Spacing Calculator
Max Area/Head: 20.9 m²Max Spacing: 4.6 m
Total Area: 100.0 m²
Heads Required (by Area): 5
Heads Required (by Grid Layout):9
Layout: 3 x 3 Grid
Spacing X: 3.3mSpacing Y: 3.3mCoverage: 11.1m²/head
*Grid ensures no distance exceeds max spacing (4.6m) and no area exceeds max coverage (20.9m²).